Monthly log

The monthly ground-level check

At least once a month, unless MassDEP approves otherwise in writing, the tank and its grounds get a ground-level inspection with a written, dated log (Chapter 8.1.22(2)).

Binoculars at a tank

Binoculars, not a climb

Climbing is not required for the monthly check; binoculars can be used for the top. Anyone who climbs follows OSHA safety rules.

A comment on every problem

Any answer that shows a problem or a coming problem gets a comment; photographs are recommended.

Kept five years

Tank inspections stay on file for MassDEP for at least 5 years, on MassDEP’s inspection reports or AWWA checklist formats (Chapter 8.1.22(5)).

The 21 checks

Item by item, as on the form

The app asks them in this order. Items about a part the tank does not have start as N/A.

  1. Are photographs to be taken during this inspection?For the record
  2. Is there damage to the fence?Problem if Yes · N/A when the tank has no fence
  3. Are there signs of vandalism?Problem if Yes
  4. Are there signs of forced entry?Problem if Yes
  5. Is there damage or corrosion to the ladder and/or cage?Problem if Yes · N/A when the tank has no exterior ladder
  6. Is the roof cover/hatch closed?Problem if No
  7. Is the roof vent screen in place and clean? (If visible from ground level)Problem if No
  8. Is the intrusion alarm operational?Problem if No · N/A when the tank has no intrusion alarm
  9. Is the tank overflowing?Problem if Yes
  10. Is overflow pipe or box cover blocked?Problem if Yes
  11. Is the ground level overflow screen in-place and intact?Problem if No
  12. Does the ground level overflow have a 12-inch minimum air gap?Problem if No
  13. Are there visible leaks?Problem if Yes
  14. Is there exterior tank corrosion?Problem if Yes
  15. Are trees or brush encroaching on the tank or structure?Problem if Yes
  16. Are there visible foundation problems (i.e. settlement, deep cracking, anchor bolts rust, etc.)?Problem if Yes
  17. Is there a working exterior sampling station for the tank?Problem if No
  18. Is the valve pit accessible and free of standing water?Problem if No · N/A when the tank has no valve pit
  19. Are the cathodic protection meter readings acceptable?Problem if No · N/A when the tank has no cathodic protection
  20. Are there signs of wind or earthquake damage?Problem if Yes
  21. Other concerns?Problem if Yes

From MassDEP PWS Monthly Storage Tank Inspection Log (Rev September 2015).

A tank site fence

Fence and gate

A closed tank hatch

Roof hatch

A screened vent

Vent screen

An overflow outlet

Overflow

A valve pit hatch in grass

Valve pit

A sampling tap box

Sampling station